After the long use of surge protection device, fire may occur due to leakage current, power consumption and temperature caused by aging of materials. Thermal stability tester is to simulate increasing leakage current of SPD to check if DUT can trip automatically during heating situation to prevent fire. It is mainly used to conduct thermal stability performance test for low voltage SPD and piezoresistor.
> measurement by PC, PLC control
> with abrupt voltage function, for test in high current condition
> with high power resistance box
> internal test box
> friendly user interface to show operating condition
> voltage, current and temperature curve drew automatically
> multiple points temperature detection
> sampling and record regularly to check and compare temperature values
> 2 times Uc leakage current test function
> RS232 communication port for remote control
Technical parameters |
||
Model |
TTS 2 |
TTS 20 |
Max.current |
1A,2A |
5A,10A,20A |
Min.current |
1mA |
2mA |
Test grade |
4-grade |
4-grade |
Current measurement resolution |
Better than 3% |
|
Test voltage |
0~1500V |
|
Voltage measurement resolution |
Better than 3% |
|
Temperature measurement |
0~200℃ |
|
Temperature measurement resolution |
Better than ±3℃ |
|
Temperature measurement path |
4-path |
|
Temperature measurement mode |
Thermoelectric couple, surface test |
|
Test box |
Internal, with SPD installation rail |
|
Voltage regulating mode |
Power-driven |
|
Continuous current |
Programmable control, automatic compensation |
|
Measurement system |
PC control, current, voltage and temperature
curve drawing
|
|
General data |
||
Power supply |
AC220V ± 10%, 50/60Hz |
|
Temperature |
-10~+40℃ |
|
Humidity |
35%~85%RH(no condensation) |
|
Ground resistance |
No more than 0.5Ω |
|
Dimension |
600×800×1720 |
|
Weight |
Approx. 200kg |
|
No conductive dust, fire and explosion danger, no corroding metal and insulated gas. Voltage waveform is sine wave. THD is <5%.
|